Modbus RTU/TCP Server User Manual for LinPAC / LinCon CONTENTS CH 1 INTRODUCTION ..............3 1-1. Install Modbus server on your LinPAC/ / / / LinCon ........4 Software Installation................4 Hardware Connection................5 CH 2 MODBUS CONTROL FUNCTION ..........7 2-1.
Modbus RTU/TCP Server User Manual for LinPAC / LinCon CH 1 Introduction This manual is written for modbus users of ICPDAS LinPAC and LinCon series, and it only supports 8K & 87K I/O Modules. This document will guid you : - How to setup Modbus Server on your devices.
Modbus RTU/TCP Server User Manual for LinPAC / LinCon 1-1. Install Modbus server on your LinPAC/ / / / LinCon Software Installation If your LinPAC/LinCon is former released, you have to install the Modebus Server by manual. STEP 1 : Download the latest Modbus Server for LinPAC/LinCon.
Modbus RTU/TCP Server User Manual for LinPAC / LinCon : : : : NOTE The LinPAC/LinCon Device Net ID must be the unique of the network. For RTU protocol, the default COM port control setting is: Baud rate : 115200 , Parity : None Data bits...
Page 6
Modbus RTU/TCP Server User Manual for LinPAC / LinCon Ordering Information : CA-0910F:9-pin Female-Female D-sub cable, 1M Cable Ver : 1.0 (2009.04)
Modbus RTU/TCP Server User Manual for LinPAC / LinCon CH 2 Modbus Control Function This chapter is about how to consist your modbus requests, and how to interpret response messages. LinPAC/LinCon Modbus Server supports functions: Function Code Sub Code Description Section Read back multiple coils status (0xxxx) for DO Read multiple input discretes (1xxxx) for DI...
Modbus RTU/TCP Server User Manual for LinPAC / LinCon 2-1. Function Code 01: : : : Read Coils (0xxxx) This function code is used to read back the ON/OFF settings of DOs. Request PDU Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5...
Modbus RTU/TCP Server User Manual for LinPAC / LinCon 2-2. Function Code 02: : : : Read Discrete Inputs (1xxxx) This function code is used to read the ON/OFF status of DIs. Request PDU Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5...
Modbus RTU/TCP Server User Manual for LinPAC / LinCon Response PDU Byte 3 ~ (Byte Count + 2) Byte 0 Byte 1 Byte 2 Device Net ID Function code Byte count Response AO values Response data length [**] two bytes / pre AO register [**] AO value is presented in a WORD signature = 2 Bytes.
Modbus RTU/TCP Server User Manual for LinPAC / LinCon [*] I-8017/I-87017 supports 5 range modes for option, you can specify following type code to interpret your response data. 0: depend on the current setting of I/O module. 1: +/- 10.0V, 2: +/- 5.0V, 3: +/- 2.5V, 4: +/- 1.25V,...
Modbus RTU/TCP Server User Manual for LinPAC / LinCon 2-6. Function Code 06: : : : Write Single Registers (4xxxx) This function code is used to write single AO for I-8024 and I-87024 modules. Request PDU Byte 0 Byte 1 Byte 2 Byte 3 Byte 4...
Modbus RTU/TCP Server User Manual for LinPAC / LinCon 2-8. Function Code 16: : : : Write Multiple Registers (4xxxx) This function code is used to set a sequence of AOs for I-8024 and I-87024 modules. Request PDU Byte 0 Byte1 Byte 2 Byte 3...
Modbus RTU/TCP Server User Manual for LinPAC / LinCon http://ftp.icpdas.com/pub/cd/8000cd/napdos/dcon/io_module/dcon/8k87k/mod ules/typetable.htm 2-9.2 Sub Function Code 07 : Set range code of AI/O module Request PDU Byte 0 Byte1 Byte 2 Byte 2 Byte 3 Byte Devic ID Address Hi Address Lo Set value Func.