APPENDIX 3 EQUIPMENT GROUPING TABLE
Equipment type
FDO181 Smoke detector
FDT181 Heat detector
FDM181 Manual Call Point
FDHM181 Hydrant Manual Call Point
FDCI181 Input module
FDCIO181 Input/output module
Main board supervision input
Main board confirmation input
Main board alarm input
Main board output, interlocking panel output (without
confirmation)
Main board output, interlocking panel output (with
confirmation)
NAC
Main power
Battery
Charging circuit
Printer
FDCL181 Isolator
FDCI181 Input module/ FDCIO181 Input/output module
supervision input
FDCI181 Input module/ FDCIO181 Input/output module
confirmation input
FDCI181 Input module/ FDCIO181 Input/output module alarm
input
FDCI181 Input module/ FDCIO181 Input/output module output
(without confirmation)
FDCI181 Input module/ FDCIO181 Input/output module output
(with confirmation)
Note:
-
One device can be assigned to max. 10 groups AND 6 FRT groups.
-
Relations among equipments of control output group is "and" relations. Relations among equipments of
supervision and detection group is "or" relations.
-
Alarm and trouble information of equipments of fire display panel group can be displayed on the display
panel.
-
Equipments must be put into groups to participate interlocking relation program.
Operating Manual of FC18 Controller
Detecting
group
Control
Supervision
output
group
√
√
√
√
√
√
√
√
√
√
√
√
Fire display
group
panel group
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
Page: 59/63