APPENDIX 3 DEVICES GROUPING TABLE
Device type
FDO181 Smoke detector
FDT181 Heat detector
FDM181 Manual Call Point
FDCI181 Input module
FDCIO181 Input/output module
Main board supervision input
Main board confirmation input
Main board alarm input
Main board output, interlocking panel output (without
confirmation)
Main board output, interlocking panel output (with
confirmation)
NAC
Main power
Battery
Charging circuit
Printer
FDCL181 Isolator
Supervision input of FDCI181 Input module/ FDCIO181
Input/output module
Confirmation input of FDCI181 Input module/
FDCIO181 Input/output module
Alarm input of FDCI181 Input module/ FDCIO181
Input/output module
Output (without confirmation) of FDCI181 Input
module/ FDCIO181 Input/output module
Output (with confirmation) of FDCI181 Input module/
FDCIO181 Input/output module
Note:
-
One device can be assigned to max. 10 groups AND 6 FRT groups.
Relations among equipments of control output group is "and" relations. Relations among equipments of
-
supervision and detecting group is "or" relations.
-
Alarm and trouble information of devices of FRT group can be displayed on the display panel.
Devices must be put into groups to participate interlocking relation program.
-
Operating Manual of FC18 Controller
Detecting
group
√
√
√
√
√
Control output
Supervision
group
group
√
√
√
√
√
√
√
√
FRT
group
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
Page: 64/70