Other Pump Controls

Prerequisite: Common parameters must first be set for each pump control below:
Parameter
Sensor Mode (2.1.2.) (Page 168) or Sensor Mode (2.1.3.) (Page 169)
Response rate in Quick Start (Page 59)
Transducer (2.1.6.) (Page 170)
Units (2.1.1.) (Page 168)
Low Calibration Point (2.2.1.) (Page 171)
High Calibration Point (2.2.2.) (Page 172)
7.7.6.1

Totalizing pumped volume

Available only on LUT430 (Pump and Flow model), and LUT440 (OCM model).
Prerequisite: The volume of the vessel must be known.
Parameter
Vessel Shape (2.6.1.)
(Page 180)
Maximum Volume (2.6.3.)
(Page 182)
Pump Control Mode (2.7.1.4.)
(Page 185) or Pump Control
Mode (2.7.1.5.) (Page 185)
ON Setpoint Pump 1 (2.7.1.6.)
(Page 186)
ON Setpoint Pump 2 (2.7.1.8.)
(Page 186)
OFF Setpoint Pump 1 (2.7.1.7.)
(Page 186)
OFF Setpoint Pump 2 (2.7.1.9.)
(Page 186)
Totalizer Decimal Position
(2.7.3.2.) (Page 195)
Totalizer Multiplier (2.7.3.3.)
(Page 195)
Inflow/Discharge Adjust
(2.7.3.4.) (Page 195)
1. Display vessel volume on the LCD (set parameter Sensor Mode (2.1.2.) (Page 168) to
VOLUME).
2. Toggle to SV on LCD to display current level (set parameter Sensor Mode Secondary
(2.1.4.) (Page 170) to LEVEL).
3. See Running Totalizer (2.7.3.1.) (Page 194) to view pumped volume.
SITRANS LUT400
Operating Instructions, 07/2019, A5E33329501-AC
Sample Value
Description
LINEAR
Vessel shape is linear (flat bottom)
17.6
Max volume is 17.6m
ADA
Sets the control algorithm used to trip the pump
relay to ALTERNATE DUTY ASSIST.
1.0 m
Sets the level at which pump 1 turns on. The
first cycle will use this setpoint. Subsequent
cycles rotate the setpoint among the pumps.
1.2 m
Sets the level at which pump 2 turns on.
0.2 m
Sets the level at which pump 1 turns off. The
first cycle will use this setpoint. Subsequent
cycles rotate the setpoint among the pumps.
0.3 m
Sets the level at which pump 2 turns off.
2 DIGITS
Sets the totalizer display to 2 digits.
1000
Actual volume is divided by 1000, prior to dis-
play on LCD.
RATE
The inflow rate measured just prior to the start
ESTIMATE
of the pump cycle is used to estimate the inflow
for the duration of the cycle.
General Operation
7.7 Pump Control
Description
Volume
Medium
XPS-10
M
1.8
0.4
or 17,600 liters.
3
113