Totalizing Pumped Volume [6 relay model]

Prerequisite: the volume of the vessel must be known.
Parameter
P001
P002
P003
P004
P005
P006
P007
P050
P051
P111
P111
P111
P112
P112
P112
P113
Set in RUN Mode
1.
Press PROGRAM
2.
Press TOGGLE
3.
Press AUXILIARY

Setting Independent Failsafe Controls

Independent failsafe controls allow you to vary an individual relay from the global failsafe
controls programmed in P070 to P072.
Example:
The global failsafe controls are set to hold and Relay Five is set to trigger an alarm bell.
Parameter
P071
P129
7ML19985FC03
Index
Value Description
G
7
G
1
G
2
G
102
G
1
G
1.8
G
1.4
G
1
G
17.6
1
52
2
52
3
52
1
1.0
2
1.2
3
1.4
0
0.2
for RUN mode.
to display pumped volume on the totalizer.
to display current level in the auxiliary reading area.
P
Index
Value Description
G
HOLd
5
dE
HydroRanger 200 – INSTRUCTION MANUAL
Operation = pumped volume
These parameters are as shown above.
Tank shape is Flat Bottom.
3
Max volume is 17.6m
Sets relays 1, 2, and 3 as a pump group using
ALTERNATE DUTY ASSIST CONTROL.
Sets the ON setpoints for the pump group.
Sets the OFF setpoints for the pump group.
Keep level at last known value.
De-energize Relay Five, and trigger alarm.
or 17,600 liters.
Page 63