Setting The Ip Address; Changing The Properties Of The S7-1500 Software Controller; Downloading A Project To The Target System - Siemens SIMATIC ET 200SP Operating Instructions Manual

Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

5. The following interfaces can be seen in the Open Controller:
– Onboard interface X2 (GB Ethernet Windows interface) that is assigned directly to the PC
– Exchangeable BusAdapter that is assigned directly to the Software Controller (2 ports)
6. The following preconfigured components can be seen in the device view:
– CPU 1515SP PC2 / CPU 1515SP PC2 F/T/TF: CPU 1505SP (F/T/TF) Software Controller
7. Insert the server module from the hardware catalog.
The server module forms the termination of the CPU with the I/O modules. If no server
module is configured, the server module is added automatically during compiling.
8.3.2

Setting the IP address

Set the IP address as follows:
• BusAdapter [X1]: The configured IP address becomes effective on the Open Controller after
a download. To go online via the [X1] interface, the configured address must match the [X1]
address entered in the panel of the software controller.
• Onboard interface [X2]: The configured IP address should be identical to the Windows IP
address of the Open Controller.
8.3.3

Changing the properties of the S7-1500 Software Controller

Information on the property of the CPU is available in the Inspector window under "Properties".
You can change these properties if required.
8.3.4

Downloading a project to the target system

Key statement
To set up your automation system, you need to download the project data you generated offline
to the connected devices. This project data is generated, for example when configuring
hardware, networks, and connections or when programming the user program or when
creating recipes. The first time you download, the entire project data is downloaded. During later
download operations, only changes are downloaded.
Proceed as follows to download the configuration:
1. Select the complete PC system in the device view.
2. Right-click on the PC system.
3. Select the option you require in the "Download to device" menu command.
Note
Note that the options available to you always depend on the selected device.
CPU 1515SP PC2 (F/T/TF)
Operating Instructions, 03/2023, A5E42603425-AC
station (1 port)
8.3 Initial commissioning an open controller
Commissioning
51