Setting A Pump Up (Reservoir) Group - Siemens HydroRanger 200 Instruction Manual

Table of Contents

Advertisement

Set Relays to ALTERNATE DUTY ASSIST
Parameter
P111
P111
P111
Set the ON Setpoints
Parameter
P112
P112
P112
Set the OFF Setpoints
Parameter
P113

Setting a Pump Up (Reservoir) Group

Sets a group of three pumps to pump up a reservoir.
7ML19985FC03
Index
Value Description
1
52
2
52
3
52
Index
Value Description
1
1.0m
2
1.1m
3
1.2m
Index
Value Description
0
0.5m
HydroRanger 200
P007
Inflow
HydroRanger 200 – INSTRUCTION MANUAL
Sets the pump relays (index 1, 2, and 3) to
ALTERNATE DUTY ASSIST.
Sets the three setpoints for the pump relays.
The first cycle will use these setpoints.
Subsequent cycles rotate the setpoints
among the pumps.
By using index 0 all six relays are set at the
same time, including any alarm relays. Use
with caution.
P006
Outflow