Allen-Bradley Powermonitor 3000 User Manual page 98

Table of Contents

Advertisement

4-38
Communications
Publication 1404-UM001D-EN-E - October 2004
Table 4.11 Ethernet Message Types
Message type
CIP PLC-5 Typed Write
CIP PLC-5 Typed Read
CIP Generic Assembly Object (class 04), Get & Set Attribute Single
for Attribute 3 (data)
CIP Generic Assembly Object (class 04), Get Attribute Single for
Attribute 3 (size)
CIP SLC 500 Typed Write
CIP SLC 500 Typed Read
CIP Data Table Read (using CSP/PCCC addressing e.g. F15:0)
CIP Data Table Write
CSP / PCCC PLC-5 Typed Write
CSP / PCCC PLC-5 Typed Read
CSP / PCCC Protected Typed Logical Read, 2 address fields
CSP / PCCC Protected Typed Logical Read, 3 address fields
CSP / PCCC Protected Typed Logical Write, 2 address fields
CSP / PCCC Protected Typed Logical Write, 3 address fields
CSP / PCCC Word Range Read
CSP / PCCC Word Range Write
CSP / PCCC Diagnostic Loopback
(1) Available in communications FRN 1.21 or later.
(2) Available in communications FRN 1.22 or later. Uses CIP Encapsulation on PCCC commands.
Ethernet PCCC/CSP protocol
PCCC messaging is supported in the Series A Powermonitor 3000 and
in Series B units with communications firmware 1.22 and Master
Module firmware 2.5x or later.
For future compatibility, it is recommended that you
IMPORTANT
use EtherNet/IP messaging with Series A
Powermonitor 3000 units.
You may set up messaging from legacy controllers such as PLC-5 and
SLC 500, to a Powermonitor 3000 with optional Ethernet
Series A
Series B
(1)
(1)
(1)
(1)
(2)
(2)
(2)
(2)
(2)
(2)