Allen-Bradley Powermonitor 3000 User Manual page 189

Table of Contents

Advertisement

DeviceNet
Element
Modbus
Element name
No.
Address
0
40401
Password
1
40402
Node address
(MAC ID)
2
40403
Baud rate
3
40404
Bus Off Interrupt
Action
4
40405
Reserved
5
40406
6
40407
7
40408
8
40409
9
40410
10
40411
11
40412
12
40413
13
40414
14
40415
15
40416
16
40417
17
40418
18
40419
19
40420
Allen-Bradley HMIs
Range
Default
Comment
Value
0 to 9999
0
Valid password required to change configuration data. Returns -1
0 to 64
63
Address 64 enables remote node address programming; there is
no actual node address of 64 defined for DeviceNet.
0 to 4
0
0 = 125k
1 = 250k
2 = 500k
3 = Auto
4 = Programmable
0 to 1
0
0 = hold CAN chip in reset
1 = reset CAN chip and continue communications
0
0
Reserved. Must be 0 on a write, returns 0
Powermonitor 3000 Data Tables
Publication 1404-UM001D-EN-E - October 2004
A-15