Allen-Bradley Powermonitor 3000 User Manual page 182

Table of Contents

Advertisement

A-8
Powermonitor 3000 Data Tables
Table A.5 Date and Time
CSP File No.
N11
Remote I/O BT
12
CIP Assy. Inst.
6 (Write), 7 (Read)
No. of Elements
8
User Configurable No
Data Type
Integer
Data Access
Read / Write
PM3000 Type
All
Element
Modbus
Element name
No.
Address
0
40101
Password
1
40102
Date: year
2
40103
Date: month
3
40104
Date: day
4
40105
Time: hour
5
40106
Time: minute
6
40107
Time: seconds
7
40108
Time: hundredths of seconds
(1) On a write, the maximum value for "day" depends on the values written to "month" and the "year".
(2) The data and time default values are set if one of the following three conditions occur:
- When the device is first powered-up at the factory
- A device power-up following the depletion of the real-time clock power source
- In the event of an abnormal condition which may cause the real-time clock to contain values which are not in the valid range
The date and time are not set to the default values when "Restore Factory Defaults" is performed via the Display Module or communications port.
Publication 1404-UM001D-EN-E - October 2004
Range
Default
Comment
(2)
Value
0 to 9999 0
Valid password required to change the date & time.
Returns -1
1998 to
1998
1 = January, 2 = February,...12 = December
2097
The internal clock adjusts the date for leap year.
1 to 12
1
(1)
1
1 to 31
0 to 23
0
0 = 12am, 1 = 1am,...23 = 11pm
The internal clock does not adjust for daylight savings time.
0 to 59
0
0 to 59
0
0 to 99
0

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1404-m41404-m61404-m51404-m8