A-20
Powermonitor 3000 Data Tables
Table A.12 Metering Demand Results
CSP File No.
F18
Remote I/O BT
25
CIP Assy. Inst.
17
No. of Elements
10
User Configurable No
Data Type
Floating point
Data Access
Read only
PM3000 Type
All
Element
Modbus
Element name
No.
Address
0
30401-02
Demand Current
1
30403-04
Demand Power
2
30405-06
Demand Reactive Power
3
30407-08
Demand Apparent Power
4
30409-10
Projected Demand I
5
30411-12
Projected Demand W
6
30413-14
Projected Demand VAR
7
30415-16
Projected Demand VA
8
30417-18
Elapsed demand period time
9
30419-20
Metering iteration
Publication 1404-UM001D-EN-E - October 2004
Units
Range
Amps (A)
21
0.0 to 999.9x10
Watts (W) 0.0 to 999.9x10
21
VAR
21
0.0 to 999.9x10
VA
21
0.0 to 999.9x10
Amps
21
0.0 to 999.9x10
Watts
21
0.0 to 999.9x10
VAR
21
0.0 to 999.9x10
VA
21
0.0 to 999.9x10
Minutes
21
0.0 to 999.9x10
-
0 to 32767
Comment
Refer to Energy Results on page 3-8.
Refer to Projected Demand Calculation on page 3-10.
The time elapsed within the current demand period.
Increments by 1 to 32767, rolls over to 0