Table 3.8 Network demand/time configuration summary
Parameter name
SNTP IP address 3, octet 1
SNTP IP address 3, octet 2
SNTP IP address 3, octet 3
SNTP IP address 3, octet 4
Controller Command
Table A.53 is a write table consisting of one integer element. A "1"
written to bit 0 signals the end of a demand period. When this occurs,
the Master Powermonitor resets this bit to 0 and sends the end of
demand broadcast to Powermonitor units configured as "Slave
broadcast input". Bits 1 through 15 are reserved.
DST (Daylight savings time) configuration
The Powermonitor 3000 may be configured to automatically adjust its
internal clock for daylight savings time. Daylight savings time
functionality is available only in Powermonitor 3000 models with
firmware revision 2.5x or later.
To set configuration options described below using the display
module, navigate through these menus: PROG. > PASS? >
CONFIGURATION > DST.
You may also configure the daylight savings time function via
communications by writing to the Daylight Savings Time
Configuration Table A.54.
DST enable
Enables the daylight savings time function. Range 0 = disable, 1 =
enable
DST start month
Selects the calendar month when daylight savings time begins. Range
1 = January, 2 = February, ... , 12 = December
DST start day
Selects the day of the week when daylight savings time begins. Range
0 = Sunday, 1 = Monday, ... , 7 = Saturday
Powermonitor 3000 Operations
Range
Default
User Setting
0-255
0
0-255
0
0-255
0
0-255
0
Publication 1404-UM001D-EN-E - October 2004
3-31