Table D.5 General Specifications
Dielectric Withstand
Terminal Blocks
Operating Temperature
Storage Temperature
Humidity
Vibration
Shock
(1)
Recommended Ring lug: AMP part # 320634
Allen-Bradley HMIs
Control Power
Voltage Inputs
Current Inputs
Status Inputs
Control Relays
Power Supply and Voltage input
Terminals
Relay, KYZ outputs, Current input
(1)
terminals
Status inputs, RS485
RIO, DNT (When present)
-20°C to +60°C (-40°F to +140°F) Cat. No. 1404-DM, 1404-Mxxxx-000, 1404-Mxxxx-DNT
+0°C to +55°C (+32°F to +131°F) 1404-Mxxxx-232, -RIO, -ENT, -CNT
-40°C to +85°C (-40°F to +185°F)
5% to 95%, Noncondensing
10 to 500 Hz: 2G Operational (±0.012 in.)
1/2 Sine Pulse, 11 ms duration: 30G Operational and 30G Nonoperational
2000 Volts
2000 Volts
2000 Volts
500 Volts
1600 Volts
12 AWG (4 mm2) max.,
9 lb-in (1.02 Nm) Torque.,
75°C or Higher Copper Wire only
14 AWG (2.5 mm2) max., 10.4 lb-in (1.18 Nm) Torque.,
75°C or Higher Copper Wire only
14 AWG (2.5 mm2) max.,
5 lb-in (0.56 Nm) Torque
14 AWG (2.5 mm2) max.,
5 lb-in (0.56 Nm) Torque
Publication 1404-UM001D-EN-E - October 2004
Technical Specifications
D-5