Allen-Bradley Powermonitor 3000 User Manual page 207

Table of Contents

Advertisement

Table A.23 Min/Max Log Configuration/Read-Back Select
CSP File No.
N26
Remote I/O BT
13
CIP Assy. Inst.
29 (Write), 30 (Read)
No. of Elements
9
User Configurable No
Data Type
Integer
Data Access
Read / Write
PM3000 Type
All
Element
Modbus
Element name
No.
Address
0
40901
Password
1
40902
Min/max parameter to read
2
40903
Read-back mode
3
40904
Enable/disable Min/max log
4
40905
Clear min/max log
5
40906
Timestamp of last min/max clear; year
6
40907
7
40908
8
40909
Allen-Bradley HMIs
Range
0 to 9999
0 to 73
0 to 1
0 to 1
0 to 1
1998 to 2097
month/day
0101 to 1231
hour/minute
0000 to 2359
second/hsec
0000 to 5999
Powermonitor 3000 Data Tables
Default
Comment
Value
0
Required for configuration, -1 for readback
select, returns -1.
1
Refer to Interfacing with the Min/Max Log
Using Communications on page 7-14
0
1
0
-
-
-
-
Publication 1404-UM001D-EN-E - October 2004
A-33

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1404-m41404-m61404-m51404-m8