Table A.4 Basic Device Configuration
CSP File No.
F10
Remote I/O BT
20
CIP Assy. Inst.
4 (Write), 5 (Read)
No. of Elements
8 (M4, M5), 9 (M6, M8)
User Configurable No
Data Type
Floating point
Data Access
Read / Write
PM3000 Type
See table
Element
Modbus
Element name
No.
Address
0
40001-2
Password
1
40003-4
Wiring mode
2
40005-6
Potential transformer (PT)
primary
3
40007-8
PT secondary
4
40009-10
I1/I2/I3 current
transformer (CT) Primary
5
40011-12
I1/I2/I3 CT secondary
6
40013-14
I4 CT primary
7
40015-16
I4 CT secondary
8
40017-18
Nominal system voltage
Allen-Bradley HMIs
M4
M
M
Range
Units
M5
6
8
• • 0 to 9999
-
• • 0 to 8
-
• • 1.0 to
Volts
10,000,000.0
• • 1.0 to 600.0
Volts
• • 1.0 to
Amps
10,000,000.0
• • 1.0 to 5.0
Amps
• • 1.0 to
Amps
10,000,000.0
• • 1.0 to 5.0
Amps
• • 1.0 to
Volts
10,000,000.0
Powermonitor 3000 Data Tables
Defaul
Comment
t
Value
0
Valid password required to change
configuration. Returns -1
6
0 = Delta 3 CT
1 = Delta 2 CT
2 = Direct Delta 3 CT
3 = Direct Delta 2 CT
4 = Open Delta 3 CT
5 = Open Delta 2 CT
6 = Wye
7 = Single Phase
8 = Demo
480.0
The high side of the PT ratio (xxx:xxx)
480.0
The low side of the PT ratio (xxx:xxx)
5.0
The high side of the CT ratio
(xxx:xxx)
5.0
The low side of the CT ratio (xxx:xxx)
5.0
The high side of the I4 CT ratio
(xxx:xxx)
5.0
The low side of the I4 CT ratio
(xxx:xxx)
480.0
Value is used in the default Sag and
Swell setpoints. (M6 and M8 only)
Publication 1404-UM001D-EN-E - October 2004