Table A.33 Harmonic Analysis Configuration/Read-Back Select
CSP File No.
N33
Remote I/O BT
14
CIP Assy. Inst.
39 (Write), 40 (Read)
No. of Elements
9
User Configurable No
Data Type
Integer
Data Access
Read /Write
PM3000 Type
See table
Applies to:
Table A.34 (All models)
Table A.35,Table A.36, Table A.37, Table A.38 (M6 & M8)
Table A.48, Table A.49 (M8 only)
Element
Modbus
M4
No.
Address
M5
0
41201
1
41202
2
41203
3
41204
4
41205
5
41206
6
41207
7
41208
8
41209
Allen-Bradley HMIs
M
M
Element name
6
8
• • Password
• • Channel
• • Read-back mode
Reserved
• • Individual harmonic data type
Reserved
• • Enable/disable Harmonics
Reserved
• • IEEE-519 Max I
Integer
sc
Reserved
• • IEEE-519 Max I
Exponent
sc
Reserved
• • IEEE 519 Max I
Integer
dmnd
Reserved
• • IEEE 519 Max I
Exponent
dmnd
Range
Default
Comment
Value
0 to 9999
0
Required for configuration, -1 for readback
select, returns -1.
1 to 9
1
Refer to Configuring Harmonic Analysis on
page 8-10
0 to 1
0
0
0
0 to 1
0
0
0
0 to 1
1
0
0
0 to 9999
0
0
0
-4 to 21
0
0
0
0 to 9999
0
0
0
-4 to 21
0
Publication 1404-UM001D-EN-E - October 2004