A-44
Powermonitor 3000 Data Tables
Table A.34 Harmonic Results; THD, Crest Factor, and More
CSP File No.
F34
Remote I/O BT
23
CIP Assy. Inst.
41
No. of Elements
9 (M4, M5); 10 (M6, M8)
User Configurable No
Data Type
Floating Point
Data Access
Read only
PM3000 Type
See table
Element
Modbus
M4
No.
Address
M5
•
0
31201-02
•
1
31203-04
•
2
31205-06
•
3
31207-08
•
4
31209-10
•
5
31211-12
•
6
31213-14
•
7
31215-16
•
8
31217-18
•
9
31219-20
Publication 1404-UM001D-EN-E - October 2004
M
M
Element name
6
8
• • Channel number
• • % IEEE THD
• • % IEC thd (DIN)
• • Crest Factor
• • THD & Crest iteration 0 to 32767
Reserved
• • TIF
Reserved
• • K-Factor
Reserved
• • IEEE-519 TDD
Reserved
• • IEEE-519 Pass/Fail
Reserved
• • FFT iteration
Range
Comment
1 to 9
Refer to Reading Harmonic Analysis Data on page 8-11
0.0 to 1000.0
0.0 to 1000.0
0.0 to 10.0
0
22
0.0 to 999.9x10
0
22
0.0 to 999.9x10
0
22
0.0 to 999.9x10
0
-1 to 1
0
0 to 32767