Table A.29 List of Event Types
Applies to:
Table A.27 Event Log Results
PM3000 Type
See table
Event
M4
M
M
Event type
Code.
M5
6
8
•
•
•
0
No event
•
•
•
1
Setpoint triggered
•
•
•
2
Setpoint released
•
•
•
3
Relay force energized
•
•
•
4
Relay force de-energized
•
•
•
5
Relay force released
•
•
•
6
Status input set
•
•
•
7
Status input cleared
•
•
•
8
KWh counter set or cleared
•
•
•
8
KVARh counter set or cleared
•
•
•
8
KVAh counter set or cleared
•
•
•
8
Ah counter set or cleared
•
•
•
8
All energy counters cleared
•
•
•
8
Trend log cleared
•
•
•
8
Min/max log cleared
•
•
•
8
Factory defaults restored
•
•
•
8
Status input #1 counter cleared
•
•
•
8
Status input #2 counter cleared
•
•
•
8
Reserved
•
•
•
8
Single setpoint timer cleared
•
•
•
8
All setpoint timers cleared
•
•
•
9
Power-up
•
•
•
10
Power-down
•
•
•
11
Selftest failure
•
•
•
12
Date/time set
•
•
•
13
Change of non-setpoint config data 0
•
•
•
14
Change of setpoint config data
•
•
•
15
NVRAM Clr
•
16
Transient detected
•
17
User Comment
•
•
•
18
External Demand Sync Timeout
•
•
•
19
Comm Card Reset
Allen-Bradley HMIs
Event Command
Comment
Code
0
The log starts with no events recorded
Setpoint Number
A setpoint activated
A previously active setpoint released
Relay Number
1 = Form C relay, 2 = KYZ
Status Input Number
1
Records command action
2
3
4
5
6
7
8
9
10
11
12
13
0
Control power was applied.
0
Control power was lost or internal reset occurred.
Status Error Code
Refer to Table A.28 Status Error Codes (bitfield)
0
The date and/or time was set or altered.
0
0
NVRAM has been cleared due to an extended loss
of control power or internal error.
User has manually entered a comment to record the
impact of an event on your plant or process.
The demand delay expired before the next expected
external demand sync
An unexpected comm card condition has been
detected and the master module has reset the
comm card in an attempt to resume normal
operation.
Powermonitor 3000 Data Tables
Publication 1404-UM001D-EN-E - October 2004
A-39