A-12
Powermonitor 3000 Data Tables
Table A.8 Optional Communication Configuration
CSP File No.
N14
Remote I/O BT
24
CIP Assy. Inst.
12 (Write), 13 (Read)
No. of Elements
20
User Configurable No
Data Type
Integer
Data Access
Read / Write
PM3000 Type
All
Ethernet
Element
Modbus
Element name
No.
Address
0
40401
Password
1
40402
IP address byte a
2
40403
IP address byte b
3
40404
IP address byte c
4
40405
IP address byte d
5
40406
Subnet mask byte a
6
40407
Subnet mask byte b
7
40408
Subnet mask byte c
8
40409
Subnet mask byte d
9
40410
Gateway IP address byte a
10
40411
Gateway IP address byte b
11
40412
Gateway IP address byte c
12
40413
Gateway IP address byte d
13
40414
Keep Alive Time (ENT Series A)
Reserved (ENT Series B)
Publication 1404-UM001D-EN-E - October 2004
Select the table that applies to your Powermontior
TIP
3000.
Range
Units
Default
Value
0 to 9999 -
0
0 to 255
-
128
1
1
Device ID Factory-assigned device ID
0 to 255
-
255
255
255
0
0 to 255
-
128
1
1
1
0 to 3600 Seconds
30
Comment
Valid password required to change
configuration data. Returns -1
Format: aaa.bbb.ccc.ddd. Static IP address
of this device (for example 130.151.32.86).
Address 0.0.0.0 enables bootp server to
assign IP address, subnet mask and
gateway. If connected to a network, IP
address must be unique. (255.255.255.255
is not permitted.)
Format aaa.bbb.ccc.ddd. Ignored if bootp
enabled.
IP address of the gateway on this subnet
used to route
messages to other subnets (wide area
networking). Ignored if bootp enabled.
The maximum time a socket is dedicated to
a connection that is not responding.
Reserved on Series B. Must be 0 on a
write, returns 0