A-4
Powermonitor 3000 Data Tables
Table A.2 Remote I/O, DeviceNet, EtherNet/IP and ControlNet I/O Messaging
CSP File No.
N/A
Remote I/O BT
N/A
CIP Assy. Inst.
1 (Read), 2 (Write)
No. of Elements
2 (Default)
User Configurable Yes (DeviceNet, EtherNet/IP and ControlNet)
Data Type
Integer (Selectable as Floating Point with DeviceNet, EtherNet/IP and ControlNet)
Data Access
Read/Write
PM3000 Type
All
Remote I/O Discrete Data Provided by Powermonitor (Remote I/O Input Data)
Element
Element name
No.
1
Relay, KYZ, and alarm bits
2
Status input bits
Publication 1404-UM001D-EN-E - October 2004
Range
Comment
-
Bit
Description
00-07
Reserved, used internally for BT information
08
Form C relay state (setpoint output flag 1)
0 = De-energized & not forced
1 = Energized & not forced
09
KYZ output state (setpoint output flag 2)
0 = De-energized & not forced
1 = Energized & not forced
10
Setpoint output flag 3 state
11
Setpoint output flag 4 state
12
Setpoint output flag 5 state
13
Setpoint output flag 6 state
14
Setpoint output flag 7 state
15
Setpoint output flag 8 state
Bit
Description
00
Status input 1 state
01
Status input 2 state
02-05
Reserved, returns 0
06
New oscillograph (M6, M8 only)
Indicates at least one capture has been triggered, saved, and is
ready to be read. This bit is cleared when all captures are cleared.
07-11
Reserved, returns 0
12-14
Reserved, used internally for BT information
15
Reserved, returns 0
Data appears in the first two words of the input
TIP
image table corresponding to the Powermonitor 3000
logical rack. For example, with the unit configured as
Rack 1, Group 1 in a 1747-SN scanner residing in Slot
2, the data will appear in words I:2.8 and I:2.9 of the
data table.