Table A.21 Trend Log Configuration/Read-Back Record Select
CSP File No.
N24
Remote I/O BT
34
CIP Assy. Inst.
26 (Write), 27 (Read)
No. of Elements
26
User Configurable No
Data Type
Integer
Data Access
Read / Write
PM3000 Type
All
Element
Modbus
Element name
No.
Address
0
40801
Password
1
40802
DeviceNet unique write
identifier
2
40803
Reserved
3
40804
Read-back mode
4
40805
Logging interval
5
40806
Logging mode
6
40807
Clear trend log command
7
40808
Total records logged x 1000
8
40809
Total records logged x 1
9
40810
Reserved
10
40811
Parameter #1 selection
11
40812
Parameter #2 selection
12
40813
Parameter #3 selection
13
40814
Parameter #4 selection
14
40815
Parameter #5 selection
15
40816
Parameter #6 selection
16
40817
Parameter #7 selection
17
40818
Parameter #8 selection
18
40819
Parameter #9 selection
19
40820
Parameter #10 selection
20
40821
Parameter #11 selection
21
40822
Parameter #12 selection
22
40823
Parameter #13 selection
23
40824
Parameter #14 selection
24
40825
Parameter #15 selection
25
40826
Parameter #16 selection
Allen-Bradley HMIs
(1) For DeviceNet Powermonitors you may configure parameters 9 through 16 but Table A.22 will return only the first 8 parameters.
Range
Default
Value
0 to 9999
0
-32768 to
0
32767
0
0
0 to 6
2
-1 to 3600
900
(15 min)
0 to 1
0
0 to 1
0
0 to 999
-
0 to 999
-
0
-
1 to 301
122
0 to 301
126
100
0
(1)
0 to 301
0
Powermonitor 3000 Data Tables
Comment
Required for configuration, -1 for readback select, returns -1.
Refer to DeviceNet Unique Write Identifier on page 4-36.
Must be 0 on a write; returns 0
Refer to Setting up the Trend Log on page 7-11, and Reading
Data from the Trend Log on page 7-12.
Expressed in seconds
-1 = synchronize logging with demand interval
0 = disable periodic logging
0 = Overwrite
1 = Fill and hold
0 = no action
1 = clear trend log; returns 0
Number of records = element 7 x 1000 + element 8
Must be 0 on a write; returns 0
Refer to Setting up the Trend Log on page 7-11.
Defaults:
Parameter 1: 122, Net Kilowatt-hours
Parameter 2: 126, Net kVAR-hours
Parameter 3: 100, Demand watts
Publication 1404-UM001D-EN-E - October 2004