Allen-Bradley Powermonitor 3000 User Manual page 228

Table of Contents

Advertisement

A-54
Powermonitor 3000 Data Tables
Table A.43 Transient Analysis Configuration/Read-Back Select
CSP File No.
F43
Remote I/O BT
44
CIP Assy. Inst.
52 (Write), 53 (Read)
No. of Elements
10
User Configurable No
Data Type
Floating Point
Data Access
Read / Write
PM3000 Type
M8 only
Applies to:
Table 43: Transient analysis metering results
Element
Modbus
Element name
No.
Address
0
-
Password
1
-
DeviceNet unique write
identifier
2
-
Capture #
3
-
Cycle #
4
-
Read-back mode
5
-
Detection mode
6
-
Reserved
7
-
Auto-threshold set command
8
-
Auto-threshold set duration
9
-
Auto-threshold set margin
10
-
Voltage trigger threshold
11
-
Current trigger threshold
12
-
Auto-threshold duration time
left
Publication 1404-UM001D-EN-E - October 2004
Range
Default
Value
0 to 9999
0
-32768 to 32767 0
0 to 6
1
1 to 12
1
0 to 1
0
0 to 3
1
0
0
0 to 1
0
1 to 3600
10
1.0 to 100.0
20.0
0.1 to 100.0
10.0
0.1 to 100.0
10.0
0
0
Comment
Required for configuration, -1 for readback select,
returns -1.
Refer to DeviceNet Unique Write Identifier on
page 4-36.
Refer to Transient Analysis Configuration on
page 8-19.

Hide quick links: