Allen-Bradley Powermonitor 3000 User Manual page 174

Table of Contents

Advertisement

8-24
Advanced Features
Publication 1404-UM001D-EN-E - October 2004
• CT primary = 100 A
• CT secondary = 5 A
• Delta voltage mode (line-to-line)
You would multiply each data point by the following factor to
correctly display the waveform:
(
Factor
=
691.1
1.414
Capture Statistics
The Capture timestamp and Capture identifier are important statistics
that identify the capture. A data client may use the Capture identifier
to associate the transient capture with corresponding metering data
and event log data.
Clear Command
Issue the Clear command parameter to clear transient captures from
non-volatile memory and provide space for new captures. Write the
correct Password for the Powermonitor 3000 to accept the command.
The command parameter options are:
-1 - Clear all transient captures
0 - No action
1 - Clear capture #1
2 - Clear capture #2
3 - Clear capture #3
4 - Clear capture #4
5 - Clear capture #5
6 - Clear capture #6
At least one capture location must be clear for a transient detect event
to be processed. If no captures are clear, the Powermonitor 3000
ignores any new transient detection events.
)
(
8192
13800
120
)
=
13.72