Allen-Bradley Powermonitor 3000 User Manual page 316

Table of Contents

Advertisement

F-10
Powermonitor 3000 EtherNet/IP Device Profile
Publication 1404-UM001D-EN-E - October 2004
The Length parameter contains the total length of the
TIP
Vendor, Serial Number and Other parameters to
follow. None of these values are actually used by the
PCCC Object, but are instead simply preserved intact
in the associated response.
The DC will respond to the Execute PCCC service with the following
response parameters, which represent a completely encapsulated
PCCC response:
Table F.20 Response Parameters
Name
Data Type
Length
USINT
Vendor
UINT
Serial Number
UDINT
Other
Product Specific
CMD
USINT
STS
USINT
TNSW
UINT
EXT_STS
USINT
PCCC results
Array of USINT
The Length parameter contains the total length of the
TIP
Vendor, Serial Number and Other parameters to
follow. None of these values are actually used by
the PCCC Object, but are instead simply preserved
intact in the associated response.
Parameter
Semantics of Values
Description
Length of Requestor
Same value as in
ID
request.
Vendor Number of
Same value as in
requester
request.
ASA serial number of
Same value as in
requestor
request.
Identifier of user,
Same value as in
task, etc. on the
request.
requester
Command Byte
Refer to PCCC
specification
Status Byte
Refer to PCCC
specification
Transport Word
None. Same value as the
request
Extended Status: not
Refer to PCCC
used for all CMD's
specification
CMD/FNC specific
Refer to PCCC
result data
specification