Allen-Bradley Powermonitor 3000 User Manual page 185

Table of Contents

Advertisement

Element
Modbus
Element name
No.
Address
4
40305
Device address
5
40306
Data format
6
40307
Inter-Character
Timeout
(1) The default address is the 'Device ID', which is factory assigned and is found on the label on the side of the master module. The device ID is incremented for each device.
Allen-Bradley HMIs
Range
Units Default
Value
1 to 247
-
(1)
0 to 2
-
0
0 to 6553 mS
0
Powermonitor 3000 Data Tables
Comment
Identifies the device on a multi-drop network. 0 is typically
used by the DF1 master. 255 is the broadcast address
Parity, number of data bits, number of stop bits
0 = No parity, 8 data bits, 1 stop bit
1 = Odd parity, 8 data bits, 1 stop bit
2 = Even parity, 8 data bits, 1 stop bit
Specifies the minimum delay between characters that
indicates the end of a message packet. 0 = 3.5 character
times.
Publication 1404-UM001D-EN-E - October 2004
A-11