Allen-Bradley Powermonitor 3000 User Manual page 231

Table of Contents

Advertisement

Table A.46 Transient Capture Results
CSP File No.
N46
Remote I/O BT
60
CIP Assy. Inst.
57
No. of Elements
29 (DeviceNet only); 59 (All other communications types)
User Configurable No
Data Type
Integer
Data Access
Read only
PM3000 Type
M8 only
Element
Modbus
Element name
No.
Address
0
-
Timestamp;
1
-
2
-
3
-
Capture #
4
-
Channel number
5
-
Block number
6
-
Reserved
7
-
Unique Transient Capture ID
8
-
Reserved
9
-
Data Point 1
10
-
Data Point 2
11
-
Data Point 3
12
-
Data Point 4
13
-
Data Point 5
14
-
Data Point 6
15
-
Data Point 7
16
-
Data Point 8
17
-
Data Point 9
18
-
Data Point 10
19
-
Data Point 11
20
-
Data Point 12
21
-
Data Point 13
22
-
Data Point 14
23
-
Data Point 15
24
-
Data Point 16
25
-
Data Point 17
26
-
Data Point 18
27
-
Data Point 19
28
-
Data Point 20
Allen-Bradley HMIs
Range
Month/day
0000 to 1231
Hour/minute
0000 to 2359
Second/hsec
0000 to 5999
1 to 6
1 to 7
See page 8-22
0
0 to 30000
0
-8192 to 8191
Powermonitor 3000 Data Tables
Comment
Capture trigger timestamp, see page 4-18.
Refer to Reading Transient Capture Data on page 8-21.
Publication 1404-UM001D-EN-E - October 2004
A-57

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1404-m41404-m61404-m51404-m8

Table of Contents