3-24
Powermonitor 3000 Operations
Table 3.7 Device Configurations Summary
Parameter
Wiring Mode
PT Primary
PT Secondary
CT Primary
CT Secondary
I4 Primary
I4 Secondary
Nominal System Voltage
(M6 and M8 only)
Publication 1404-UM001D-EN-E - October 2004
Password
The password protects the unit against unauthorized commands or
configuration changes. Be sure to write down the new password and
keep it in a safe place. Range 0 to 9999, default 0000.
If you forget or lose your password, contact
TIP
Rockwell Automation Technical Support for
assistance. Refer to Rockwell Automation Support on
the back cover of this manual.
Range
0 = Delta 3 CT
5 = Open Delta 2 CT
1 = Delta 2 CT
6 = Wye
2 = Direct Delta 3 CT
7 = Single Phase
3 = Direct Delta 2 CT
8 = Demo
4 = Open Delta 3 CT
1 to 10,000,000
1 to 600
1 to 10,000,000
1 to 5
1 to 10,000,000
1 to 5
1 to 10,000,000
Default
User Setting
6 = Wye
480
480
5
5
5
5
480