Table A.6 Advanced Device Configuration
CSP File No.
N12
Remote I/O BT
26
CIP Assy. Inst.
8 (Write), 9 (Read)
No. of Elements
25
User Configurable No
Data Type
Integer
Data Access
Read / Write
PM3000 Type
All
Element
Modbus
Element name
No.
Address
0
40201
Password
1
40202
New password
2
40203
Demand period length
3
40204
Number of demand periods
4
40205
Predicted demand type
5
40206
KYZ control source
6
40207
KYZ pulse output scale
7
40208
KYZ pulse output width
8
40209
Relay control source
9
40210
Relay pulse output scale
10
40211
Relay pulse output width
11
40212
RMS resolution
12
40213
RMS result averaging
13
40214
Frequency averaging
14
40215
Restore factory default
config
15
40216
Clear status input counters
16
40217
Wdog action
Allen-Bradley HMIs
Range
Units Default
Value
0 to 9999 -
0
0 to 9999 -
-1
-99 to
Min
15
+99
1 to 15
-
1
0 to 2
-
0
0 to 8
-
7
1 to
-
10
30000
0, 40 to
mSec 0
2000
0 to 8
-
7
1 to
-
10
30000
0, 40 to
mSec 100
2000
0 to 1
-
0 (M4)
1 (M5, 6 or 8)
0 to 1
-
0 (M4)
1 (M5, 6 or 8)
0 to 1
-
1
0 to 1
-
0
0 to 3
-
0
0 to 1
-
1
Powermonitor 3000 Data Tables
Comment
Required to change configuration data.
Returns -1
-1 = no action; 0 to 9999 = new password;
returns -1
Refer to Demand Calculation on page 3-9
0 = instantaneous; 1 = 1st order; 2 = 2nd order
0 = None (forcing
5 = Vah
only)
6 = Ah
1 = Wh Forward
7 = Setpoints
2 = Wh Reverse
8 = Discrete control (RIO,
3 = VARh Forward
DeviceNet)
4 = VARh Reverse
Refer to Relay and KYZ Output Operations on
page 6-1
0 = KYZ-style transition
40 to 2000 = pulse duration
Same choices as KYZ control source
Refer to Relay and KYZ Output Operations on
page 6-1
0 = KYZ-style transition
40 to 2000 = pulse duration
0 = Nominal
1 = High
0 = No averaging.
1 = Average of the last 8 results
0 = none; 1 = last 8 cycles
0 = No action 1 = Restore factory default settings
0 = No action
2 = Clear counter #2
1 = Clear counter #1
3 = Clear both
0 = Restart, log an event and halt operation
1 = Restart, log an event and resume
Refer to Watchdog Timeout Action on page 3-28.