F-4
Powermonitor 3000 EtherNet/IP Device Profile
Publication 1404-UM001D-EN-E - October 2004
Table F.7 Request Parameters
Parameter
Data Type Description
Type
USINT
Behavior
The Powermonitor 3000 system's Identity instances handle reset
services in the following manner regardless of the reset type
requested:
Instance 1 (PM 3000) – Respond successfully to the request, but
continue normal operation.
Instance 2 (DC) – Respond successfully to the request and notify the
PM 3000 to reset the DC.
Get Attribute Single Service
The Get Attribute Single service returns the single attribute specified
by the parameter Attribute ID.
Table F.8 Request Parameters
Parameter
Data Type Description
Attribute ID
UINT
Identity Object Instances
The DC's Identity Object supports the following instances:
Instance 1 (PM 3000)
Instance 1 represents the PM 3000 device. Since instance 1 of the
Identity Object is the one which is browsed by RSLinx, the complete
device (i.e. the PM 3000 with DC) will appear in RS Who as a PM 3000
rather than a DC.
Instance 1 of the Identity Object reports the following instance
specific attribute values:
Type of Reset to perform
Identifies the attribute to be read / returned