Allen-Bradley Powermonitor 3000 User Manual page 200

Table of Contents

Advertisement

A-26
Powermonitor 3000 Data Tables
Table A.18 Setpoint Setup/Read-Back Select and Status
CSP File No.
N23
Remote I/O BT
22
CIP Assy. Inst.
24 (Write), 25 (Read)
No. of Elements
16
User Configurable No
Data Type
Integer
Data Access
Read / Write
PM3000 Type
All
Element
Modbus
Element name
No.
Address
0
40701
Password
1
40702
Setpoint number
2
40703
Read-back mode
3
40704
Setpoint type
4
40705
Evaluation condition 0 to 5
5
40706
High limit
Integer
6
40707
High limit Exponent
7
40708
Low limit
Integer
8
40709
Low Limit Exponent
9
40710
Action delay
10
40711
Release delay
11
40712
Output action
12
40713
Status
13
40714
Accumulated time
Integer
14
40415
Accumulated time
Exponent
15
40716
Clear time
accumulator
command
(1) On the M6 and M8, setpoint #19 and #20 default to detect voltage sag and voltage swell. See Sag and Swell, page 8-13
Publication 1404-UM001D-EN-E - October 2004
Range
Units
0 to 9999
-
1 to 10 (M4, M5)
-
1 to 20 (M6, M8)
0 to 1
-
0 to 52
-
-
0 to 9999
Depends
on
setpoint
type
-4 to 21
0 to 9999
-4 to 21
0-3600 (M4, M5)
Seconds
0-30000 (M6, M8)
(M4, M5)
.1 Sec
(M6, M8)
0-3600 (M4, M5)
Seconds
0-30000 (M6, M8)
(M4, M5)
.1 Sec
(M6, M8)
0 to 32 (M4, M5)
-
0 to 43 (M6, M8)
0 to 1
-
0 to 9999
Seconds
-1 to 21
-
0 to 1
-
Default
Comment
Value
0
Required for configuration, -1 for readback
select, returns -1.
-
Refer to Writing Setpoint Configuration Using
Communications on page 5-11.
0
(1)
0
0
(1)
0
(1)
0
(1)
0
(1)
0
0
0
(1)
0
0
-
-
0