Allen-Bradley Powermonitor 3000 User Manual page 229

Table of Contents

Advertisement

Table A.44 Transient Analysis Metering Results
CSP File No.
F44
Remote I/O BT
32
CIP Assy. Inst.
54
No. of Elements
14
User Configurable No
Data Type
Floating Point
Data Access
Read only
PM3000 Type
M8 only
Element
Modbus
Element name
No.
Address
0
-
Capture number
1
-
Cycle number
2
-
L1-L2 or L1-N Voltage
3
-
L2-L3 or L2-N Voltage
4
-
L3-L1 or L3-N Voltage
5
-
L1 Current
6
-
L2 Current
7
-
L3 Current
8
-
L4 Current
9
-
Voltage Index at trigger
10
-
Current Index at trigger
11
-
Voltage Trigger Threshold
12
-
Current Trigger Threshold
13
-
Unique Transient Capture ID
Allen-Bradley HMIs
Range
Comment
1 to 6
Refer to Reading Transient Analysis Metering Data on
page 8-20.
1 to 12
21
0.0 to 999.9x10
21
0.0 to 999.9x10
21
0.0 to 999.9x10
21
0.0 to 999.9x10
21
0.0 to 999.9x10
21
0.0 to 999.9x10
21
0.0 to 999.9x10
3
3
-999.0x10
to 999.0x10
3
3
-999.0x10
to 999.0x10
3
0.0 to 999.0x10
3
0.0 to 999.0x10
0 to 30000
Powermonitor 3000 Data Tables
Publication 1404-UM001D-EN-E - October 2004
A-55

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1404-m41404-m61404-m51404-m8

Table of Contents