Allen-Bradley Powermonitor 3000 User Manual page 230

Table of Contents

Advertisement

A-56
Powermonitor 3000 Data Tables
Table A.45 Transient Capture Clear/Read-Back Data Select
CSP File No.
N45
Remote I/O BT
17
CIP Assy. Inst.
55 (Write), 56 (Read)
No. of Elements
13
User Configurable No
Data Type
Integer
Data Access
Read / Write
PM3000 Type
M8 only
Applies to:
Table 45: Transient capture results
Element
Modbus
Element name
No.
Address
0
-
Password
1
-
Dnet unique write
identifier
2
-
Capture number
3
-
Channel number
4
-
Block number
5
-
Read-back mode
6
-
Clear command
7
-
Reserved
8
-
Reserved
9
-
Reserved
10
-
Capture clear status
11
-
Capture ready status
12
-
Reserved
Publication 1404-UM001D-EN-E - October 2004
Range
Default
Value
0 to 9999
0
-32768 to 32767
0
0 to 6
1
1 to 7
1
See page 90
1
0 to 2
0
0 to 3
0
0
0
0
0
0
0
0 to 63
-
0 to 63
-
0
0
Comment
Required for configuration, -1 for readback select, returns
-1.
Refer to DeviceNet Unique Write Identifier on page 4-36.
Refer to Reading Transient Capture Data on page 8-21.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1404-m41404-m61404-m51404-m8

Table of Contents