Allen-Bradley Powermonitor 3000 User Manual page 56

Table of Contents

Advertisement

3-30
Powermonitor 3000 Operations
Publication 1404-UM001D-EN-E - October 2004
Time IP address
The IP address of the primary SNTP server, accessed as the 1
th
4
octet
World time zone
Sets the time zone of the Powermonitor 3000. Range: -12 = GMT -
12:00 - Eniwetok, Kwajalein; -11 = GMT - 11:00 - Midway Island,
Samoa; ...; 12 = GMT - 12:00; Fiji, Kamchatka, Marshall Island.
Time-set interval
Determines how often the unit time is automatically set, in seconds.
Range: 0 to 32,766. 0 = Disables the time set function, Default = 60
SNTP address 2
The IP address of the primary SNTP server, accessed as the 1
th
4
octet. Available only in master module firmware version 2.5x and
later
SNTP address 3
The IP address of a third SNTP server, accessed as the 1
octet. Available only in master module firmware version 2.5x and later
Table 3.8 Network demand/time configuration summary
Parameter name
Input mode
Broadcast port number
Time server IP address-byte 1
Time server IP address-byte 2
Time server IP address-byte 3
Time server IP address-byte 4
Time zone
Time set update interval
SNTP IP address 2, octet 1
SNTP IP address 2, octet 2
SNTP IP address 2, octet 3
SNTP IP address 2, octet 4
Range
Default
User Setting
0-3
3
300 to 400
300
0 to 255
0
0 to 255
0
0 to 255
0
0 to 255
0
-12 to 12
0
0 to 32766
60
0-255
0
0-255
0
0-255
0
0-255
0
st
through
st
through
st
th
through 4

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1404-m41404-m61404-m51404-m8

Table of Contents