Allen-Bradley Powermonitor 3000 User Manual page 302

Table of Contents

Advertisement

D-4
Technical Specifications
Publication 1404-UM001D-EN-E - October 2004
General Input, Output, and Environmental Ratings
Table D.2 Input and Output Ratings
Control Power
1404-xxxxA-xxx
1404-xxxxB-xxx
Voltage Sense
Input Impedance: 1M ohm minimum, 399V ac maximum; V1, V2 and
Inputs: V1, V2, V3
V3 to N.
Current Sense
Overload Withstand:
Inputs: I1, I2, I3, I4
15 Amps Continuous,
200 Amps for one second
Burden: 0.05 VA
Impedance: 0.002 ohms
Maximum Crest Factor at 5A is 3
Starting Current: 5 mA
Status Inputs
Contact Closure (Internal 24Vdc)
Control Relay
(1) ANSI C37.90-1989 trip duty
KYZ Output
(1) Solid State KYZ - 80mA at 240Vdc-300Vdc
(1)
Table D.3 Control Relay
Rating
Maximum Resistive Load
Switching
Minimum Load Switching
UL 508, CSA 22.2, IEC Rating
Class
Maximum Make Values
(Inductive Load)
Maximum Break Values
(Inductive Load)
Maximum Motor Load
Switching
(1)
Meets ANSI/IEEE C37.90-1989 standards for trip duty.
(1)
Table D.4 Relay Life
Parameter
Mechanical
Electrical
(1)
Meets ANSI/IEEE C37.90-1989 standards for trip duty.
102V-264V ac 47-63 Hz or
106V-275V dc
(0.2 Amp maximum loading)
18V to 50V dc (15 VA maximum loading)
50/60 Hz AC rms
10A at 250V
(2500VA)
10mA at 24V
B300
30A at 120V
15A at 240V
(3600VA)
3A at 120V
1.5A at 240V
(360VA)
1/3 HP at 125V
1/2 HP at 250V
Number of Operations
6
5 X 10
5
1 X 10
DC
10A at 30V and 0.25A at
250V
10mA at 24V
Q300
0.55A at 125V
0.27A at 250V
(69VA)
0.55A at 125V
0.27A at 250V
(69VA)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1404-m41404-m61404-m51404-m8

Table of Contents