A-16
Powermonitor 3000 Data Tables
RS-232
Element
Modbus
Element name
No.
Address
0
40401
Password
1
40402
Hardware port
2
40403
Protocol
3
40404
Delay
4
40405
Baud rate
5
40406
RS-232 address
6
40407
Data format
7
40408
Flow Control
(Handshaking)
8
40409
RTS On Delay
9
40410
10
40411
11
40412
Reserved
12
40413
13
40414
14
40415
15
40416
16
40417
17
40418
18
40419
19
40420
(1) The default address is the same as the 'Device ID', which is assigned at the factory and can be found printed on the white label on the side of the master module. The device ID is
incremented for each device.
Publication 1404-UM001D-EN-E - October 2004
Range
Default
Comment
Value
0 to 9999
0
Required to change configuration data. Returns -1
0 to 1
0
Select active port
0 = RS-232 port
1 = Native RS-485 port
0
0
0 = DF1 half-duplex slave
0 to 15
2 (10mS)
Specifies the delay before responding to an external request.,
useful with slow external devices (such as RF modems)
0 to 4
3
0 = 1200 baud
1 = 2400 baud
2 = 4800 baud
3 = 9600 baud
4 = 19200 baud
1 to 254
(1)
Identifies the device on the link. 0 is typically used by the DF1
master. 255 is the broadcast address
0 to 2
0
Parity, number of data bits, number of stop bits
0 = No parity, 8 data bits, 1 stop bit
1 = Even parity, 8 data bits, 1 stop bit
2 = Odd parity, 8 data bits, 1 stop bit
0 to 1
0
Data flow control for RS-232/RS-485 port.
0 = None
1 = Hardware RTS/CTS
0 to 9995
0
ms
Specifies the minimum delay between characters that indicates
the end of a message packet. 0 = 3.5 character times.
0
0
Reserved. Must be 0 on a write, returns 0