Table A.15 Metering Reactive Energy and Amp-Hour Results
CSP File No.
N21
Remote I/O BT
30
CIP Assy. Inst.
21 (Write), 22 (Read)
No. of Elements
23
User Configurable No
Data Type
Integer
Data Access
Read/Write
PM3000 Type
All
Element
Modbus
Element name
No.
Address
0
40601
Password
1
40602
Parameter select
2
40603
KVARh forward
3
40604
4
40605
5
40606
6
40607
7
40608
KVARh reverse
8
40609
9
40610
10
40611
11
40612
12
40613
KVARh net
13
40614
14
40615
15
40616
16
40617
17
40618
KAh
18
40619
19
40620
20
40621
21
40622
22
40623
Metering iteration
Allen-Bradley HMIs
Range
Units
0 to 9999
-
0 to 7
-
9
-999 to 999
kVARh
### x 10
6
### x 10
3
### x 10
0
### x 10
-3
### x 10
9
-999 to 999
### x 10
6
### x 10
3
### x 10
0
### x 10
-3
### x 10
-999 to 999
9
### x 10
6
### x 10
3
### x 10
0
### x 10
-3
### x 10
9
-999 to 999
kAh
### x 10
6
### x 10
3
### x 10
0
### x 10
-3
### x 10
0 to 32767
-
Powermonitor 3000 Data Tables
Default
Comment
Value
0
Required to clear or preset energy counters.
Returns -1.
Refer to How to Clear or Preset Energy
Counters Using Communications on
page 4-52.
Increments by 1 to 32767, rolls over to 0
Publication 1404-UM001D-EN-E - October 2004