Allen-Bradley Powermonitor 3000 User Manual page 120

Table of Contents

Advertisement

5-6
Setpoint Programming and Operation
Table 5.1 Setpoint Configuration
Parameter Name
Parameter Description
Setpoint Low Limit
The value being used as a reference to
deactivate the setpoint for over comparisons,
or to activate the setpoint for under
comparisons.
Setpoint Action Delay The minimum time in seconds that the
setpoint limit must be exceeded continuously
before the setpoint will trigger.
Setpoint Release
The minimum time in seconds that the
Delay
setpoint limit must not be exceeded
continuously before the setpoint releases.
Setpoint Action Type
The action that occurs when the setpoint is
triggered.
Clear Accumulated
Clear the time accumulator for this setpoint
Time
Publication 1404-UM001D-EN-E - October 2004
Range
0 to 10,000,000
0 to 3600
0 to 30,000
0 to 3600
0 to 30,000
0 to 32 (see details in
Table 5.3)
Yes
No
Units
Default
Depends on type
0
Sec (M4, M5)
0
0.1 Sec (M6, M8)
Sec (M4, M5)
0
0.1 Sec (M6, M8)
0
N/A