Allen-Bradley Powermonitor 3000 User Manual page 19

Table of Contents

Advertisement

Allen-Bradley HMIs
DeviceNet Optional Communications
A catalog number ending in -DNT specifies a Powermonitor 3000 with
a DeviceNet port in addition to the native RS-485 port. The DeviceNet
option permits concurrent use of both communications ports. The
DeviceNet port has the following performance features:
• Adapter class device
• Four baud settings: 125k, 250k, 500k and AutoBaud
• Remotely settable baud rate
• Cable length up to 500 meters maximum
• Node capacity up to 64 nodes including master
• Remotely settable node address
• Shielded twisted-pair media containing both signal and power
conductors
• Update rates for I/O channel: 100 mSec minimum
• Update rates for explicit messaging: 250 mSec minimum
• Configurable I/O channel assembly instance: six parameters
default, twenty-three maximum
• Configurable explicit assembly instance: seventeen parameters
default, twenty-three parameters maximum
• Explicit assembly instances for access to all data
• Two I/O assembly instances
• May be reset remotely through Identity Object
• Support for up to four concurrent clients
• Supports DeviceNet heartbeat facility
Ethernet Optional Communications
A catalog number ending in -ENT specifies a Powermonitor 3000 with
one active 10BaseT Ethernet communication port in addition to the
native RS-485 port. The Ethernet port has the following performance
features:
• Connect to Allen-Bradley PLC-5E, SLC 5/05, ControlLogix
Ethernet Bridge and the 1761-NET-ENI module products
• Built-in Internet web page support
• Compatible with RSPower32, RSEnergyMetrix, RSView32 and
RSTrend™ software
• Ethernet communication rate: 10Mbps (Series A)
10/100Mbps (Series B)
Product Description
Publication 1404-UM001D-EN-E - October 2004
2-7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1404-m41404-m61404-m51404-m8