A-6
Powermonitor 3000 Data Tables
Table A.3 Discrete Data
CSP File No.
N9
Remote I/O BT
10
CIP Assy. Inst.
3
No. of Elements
6
User Configurable No
Data Type
Integer
Data Access
Read Only
PM3000 Type
All
Element
Modbus
Element name
No.
Address
0
30001
Relay output status
1
30002
Solid-state KYZ output
status
2
30003
Alarm output word
3
30004
Status inputs state
4
30005
Status input #1 counter 0 to
5
30006
Status input #2 counter
Publication 1404-UM001D-EN-E - October 2004
Range
Comment
0 to 3
0 = De-energized & not forced
1 = Energized & not forced
2 = Force De-energized
3 = Force Energized
0 to FFFF Bitfield indicating state of the 16 alarm output flags; 0 = released, 1 = asserted.
Bit 0 = relay/setpoint output flag 1
Bit 1 = KYZ/setpoint output flag 2
Bit 2 = setpoint output flag 3
...
Bit 15 = setpoint output flag 16
0 to 3
Bit 0 = status input #1; 0 = open, 1 = contact closure detected
Bit 1 = status input #2; 0 = open, 1 = contact closure detected
Bit 2 = demand sync timeout; 1 = the demand delay expired before the next
expected external demand sync. This bit clears when the next external demand
sync occurs. Refer to Table A.6 Advanced Device Configuration element 23.
Bits 3-15 = unused (always 0)
Counts to 29,999,rolls over to 0
29999