Configuring the Time-of-Use Log
Perform a table write to Table A.55 Time-of-Use Configuration Table
to set up the user-selectable options. This read/write table of 10
integer elements contains the following configuration and read-back
selection parameters.
• Password – required for configuration. Use a valid password or
-1 for read-back select. Range 0 – 9999, default 0, returns -1
• Record to read back – selects the record to be returned in the
next read of Tables A.56, A.57 and A.58. Range 0 to 12, default 0
• Write command – stores record 0 to record 1 and shifts
remaining records down. Range 0 (no action), 1 (execute write
command), default 0
• Log day – selects the day of the month to automatically store the
in-process record and shift the remaining records down. Range 0
to 31. 0 disables automatic store. 1 to 28 select the day of month,
29 to 31 select last day of month
• Off-peak day – selects day(s) of week during which all hours are
off-peak. Bitfield, bit 0 = Sunday, bit 1 = Monday and so on.
Range 0 to 127 (0 – FF Hex), default 65 (41 Hex, Saturday and
Sunday)
• Mid peak AM – selects morning mid peak time-of-use hours.
Bitfield, range 0 to 4095 (0 to 0FFF hex). See Time-of-use
selection above. Default 1792 (700 Hex, 8:00 to 10:59 a.m.)
• Mid peak PM – selects afternoon mid peak time-of-use hours.
Default 120 (78 Hex, 3:00 to 6:59 p.m.)
PM
0
1
1
1
1
0
0
1
(1)
X
X
X
1
1
X
Data Logging
0
0
0
0
0
0
0
1
1
0
0
0
0
0
Publication 1404-UM001D-EN-E - October 2004
7-17

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1404-m41404-m61404-m51404-m8

Table of Contents