Allen-Bradley Powermonitor 3000 User Manual page 34

Table of Contents

Advertisement

3-8
Powermonitor 3000 Operations
Table 3.4 Power and Power Factor Results
Parameter
Phase 1 Distortion Power Factor
Phase 2 Distortion Power Factor
Phase 3 Distortion Power Factor
Total Distortion Power Factor
Phase 1 Displacement Power Factor
Phase 2 Displacement Power Factor
Phase 3 Displacement Power Factor
Total Displacement Power Factor
Publication 1404-UM001D-EN-E - October 2004
Description
The ratio between the magnitude of the
fundamental and the sum of the magnitudes for
all of the current harmonics for an individual
phase or all three phases.
The cosine of the phase angle between the
fundamental voltage and current for an
individual phase or all three phases; signed to
show lead (+) or lag (-).
Figure 3.1 Explanation of Power Factor Values
(Power Factor
Leading)
(+)
Pf = 100%
180˚
-kW (Export)
kWH-R (Reverse)
(Power Factor
Lagging)
(-)
Energy Results
The Powermonitor 3000 calculates energy values including kWh
forward, reverse and net; kVAh; kVARh forward, reverse and net; and
kAh. You may read these values using the Display Module or via
communications.
Range
0 to 100
-100 to 100
Pf = 0
+kVAR (Import)
kVARHR-F (Forward)
90˚
(Power Factor
Lagging)
(-)
I
II
III
IV
(Power Factor
Leading)
(+)
270˚
Pf = 0
-kVAR (Export)
kVARHR-R (Reverse)
Units
Percent
Percent
Pf = 100%
+kW (Import)
kWH-F (Forward)