Allen-Bradley Powermonitor 3000 User Manual page 192

Table of Contents

Advertisement

A-18
Powermonitor 3000 Data Tables
Table A.10 Metering Sequence Voltage and Current Results
CSP File No.
F16
Remote I/O BT
27
CIP Assy. Inst.
15
No. of Elements
11
User Configurable No
Data Type
Floating point
Data Access
Read only
PM3000 Type
All
Element
Modbus
Element name
No.
Address
0
30201-02
L4 (Zero sequence) Current
1
30203-04
Positive Sequence Current
2
30205-06
Negative Sequence Current
3
30207-08
% Current unbalance
4
30209-10
Positive Sequence Voltage
5
30211-12
Negative Sequence Voltage
6
30213-14
% Voltage unbalance
7
30215-16
Phase rotation
8
30217-18
Average frequency
9
30219-20
Frequency source
10
30221-22
Metering iteration
Publication 1404-UM001D-EN-E - October 2004
Units
Range
Amps (A)
21
0.0 to 999.9x10
21
0.0 to 999.9x10
21
0.0 to 999.9x10
Per Cent
0.0 to 100.0
Volts (V)
21
0.0 to 999.9x10
21
0.0 to 999.9x10
Per Cent
0.0 to 100.0
-
0 to 2
Hertz (Hz) 40.0 to 75.0
-
0 to 2
-
0 to 32767
Comment
Refer to Symmetrical Component Analysis
Results on page 3-5.
0 = No rotation
1 = ABC rotation
2 = ACB rotation
Average of the last 1 or 8 cycles.
Returns 0 or 999.0 if out of range
0 = V1, 1 = V2, 2 = V3
Increments by 1 to 32767, rolls over to 0