While message is pending bring back the CIP message control status.
Message Pending
B3:0
0000
0
After setting up N9 CIP_SETUP file, turn on bit N9:11/1 to start the read transfer from the power monitor. This process clears
words of N7:0 CIP message file. Copies the request from the CIP_SETUP file to N7 first 9 words. Moves a 0 to M0 scanner locat
M0:3.1009 (This loacation needs to be set to 0 when requesting information.) Enable the transfer by turning bit N7:0/15 EN to
request information into the request area of the M0 file offset 1000 + 9. Set the bit for Message Pending.
Perform Read
Message Pending
N9:11
0001
1
Allen-Bradley HMIs
Powermonitor 3000 Ladder Example for SLC through SCNR
B3:0
0
Sample Applications
COP
COP
Copy File
Source #M0:3.1000
Dest
#N7:0
Length
10
FLL
FLL
Fill File
Source
0
Dest
#N7:0
Length
9
COP
COP
Copy File
Source
#N9:0
Dest
#N7:0
Length
9
MOV
MOV
Move
Source
0
0<
Dest
M0:3.1009
?<
Enable Transfer Bit
N7:0
L
15
COP
COP
Copy File
Source
#N7:0
Dest
#M0:3.1000
Length
9
Message Pending
B3:0
L
0
Publication 1404-UM001D-EN-E - October 2004
C-37
out the first 9