Allen-Bradley Powermonitor 3000 User Manual page 193

Table of Contents

Advertisement

Table A.11 Metering Power Results
CSP File No.
F17
Remote I/O BT
31
CIP Assy. Inst.
16
No. of Elements
13
User Configurable No
Data Type
Floating point
Data Access
Read only
PM3000 Type
All
Element
Modbus
Element name
No.
Address
0
30301-02
L1 Real Power
1
30303-04
L2 Real Power
2
30305-06
L3 Real Power
3
30307-08
Total Real Power
4
30309-10
L1 Reactive Power
5
30311-12
L2 Reactive Power
6
30313-14
L3 Reactive Power
7
30315-16
Total Reactive Power
8
30317-18
L1 Apparent Power
9
30319-20
L2 Apparent Power
10
30321-22
L3 Apparent Power
11
30323-24
Total Apparent Power
12
30325-26
Metering iteration
Allen-Bradley HMIs
Units
Range
Watts (W) 0.0 to 999.9x10
22
22
0.0 to 999.9x10
22
0.0 to 999.9x10
22
0.0 to 999.9x10
Volt-amps
22
0.0 to 999.9x10
reactive
22
0.0 to 999.9x10
(VAR)
22
0.0 to 999.9x10
22
0.0 to 999.9x10
Volt-amps
22
0.0 to 999.9x10
(VA)
22
0.0 to 999.9x10
22
0.0 to 999.9x10
22
0.0 to 999.9x10
-
0 to 32767
Powermonitor 3000 Data Tables
Comment
Real power per phase, signed to show
direction.
Refer to Power Results on page 3-6.
Total power signed to show direction.
Reactive power per phase, signed to show
direction.
Total reactive power, signed to show
direction.
Apparent power per phase.
Total apparent power
Increments by 1 to 32767, rolls over to 0
Publication 1404-UM001D-EN-E - October 2004
A-19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1404-m41404-m61404-m51404-m8

Table of Contents