Note
Shield connection
The shield connection plate is fitted to the Motor Module in the delivery state. The associated
shield connection clamp can be found in the terminal kit.
Note
Protective conductor connection (PE)
On the 100 mm module illustrated above, the protective conductor connection is located on
the left next to the shield connection plate. On a 50 mm module, the protective conductor
connection is behind the shield connection plate. For more detailed information, refer to
Chapter "Protective conductor connection (PE)" (Page 49).
3.2.2.2

X1/X2 motor and brake connection

Table 3- 1
Motor holding brake connection
To ensure reliable opening of the motor holding brake, it requires a 24 V ± 10% voltage
supply at the motor connection. It must be taken into account that voltage dips can occur
along the supply cable.
● Use a Control Supply Module or a regulated DC power supply, whose setpoint is set to
26 V.
● Use supply cables with a minimum cross-section of 1.5 mm
100 m.
Power Units in Booksize C/D-Type Format
Manual, 01/2017, 6SL3097-4AC20-0BP1
X1: Motor and brake connection for Single Motor Modules 3 A to 30 A
X1 - X2: Motor and brake connection for Double Motor Modules 2 x 3 A to 2 x 18 A
Terminal
BR+
BR-
PE
U2
V2
W2
Motor Modules in booksize C/D-type format
3.2 Motor Modules with internal air cooling
Technical data
Brake connection:
Supply voltage: 24 V DC ±10 %
Maximum load current: 2 A
Minimum load current: 0.1 A
Motor connection
and a maximum length of
2
45