Line/Load Connection; Drive-Cliq Interface X500 - Siemens SINAMICS S120 Manual

Chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line-side power components
2.6 Active Interface Modules
2.6.3.3

Line/load connection

Table 2- 23
Connections for the Active Interface Module
Terminals
X1: L1, L2, L3
X2: U2, V2, W2
K4: 2/T1, 4/T2, 6/T3
(for frame sizes HI / JI
only)
PE connection
) Dimensions for connecting alternative cable lugs, see "cable lugs" in the appendix.
1
2.6.3.4

DRIVE-CLiQ interface X500

Table 2- 24
DRIVE-CLiQ interface X500
PIN
1
2
3
4
5
6
7
8
A
B
Blanking plate for DRIVE-CLiQ interfaces (50 pcs.) order number: 6SL3066-4CA00-0AA0
70
Designations
Voltage:
3 AC 380 V -10 % (-15 % < 1 min) ... 3 AC 480 V +10 %
3 AC 500 V -10 % (-15 % < 1 min) ... 3 AC 690 V +10 %
Frequency: 47 ... 63 Hz
Connecting thread:
Frame sizes FI / GI: M10 / 25 Nm for cable lugs in accordance with DIN 46234 /
DIN 46235
1)
Frame sizes HI / JI: M12 / 50 Nm for cable lugs in accordance with DIN 46234 /
DIN 46235
1)
Connection for pre-charging circuit directly on pre-charging contactor:
Frame size HI: 2 x 16 mm² max. (3RT1034)
Frame size JI: 2 x 35mm² max. (3RT1044)
Connecting thread:
Frame sizes FI / GI: M10 / 25 Nm for cable lugs in accordance with DIN 46234 /
DIN 46235
1)
Frame sizes HI / JI: M12 / 50 Nm for cable lugs in accordance with DIN 46234 /
DIN 46235
1)
Signal name
TXP
TXN
RXP
Reserved, do not use
Reserved, do not use
RXN
Reserved, do not use
Reserved, do not use
+ (24 V)
M (0 V)
Technical specifications
Transmit data +
Transmit data -
Receive data +
Receive data -
24 V power supply
Electronics ground
Manual, (GH3), 01/2013, 6SL3097-4AE00-0BP3