Operation of the line connection components via an autotransformer

An autotransformer can be used to adapt the voltage in the range up to 480 V 3 AC +10 %.
To ensure protective separation an isolating transformer must be used for voltages greater
than 480 V 3 AC +10 %.
Applications:
● The motor insulation must be protected from excessive voltages.
● The active line module must provide a stabilized DC link voltage. This is possible with a
Booksize Power Units
Equipment Manual, (GH2), 07/2007, 6SL3097-2AC00-0BP5
DANGER
rated voltage of 380 V to 415 V.
A combination with motors that may be operated with a DC link voltage of up to 660 V,
and a line voltage > 415 V requires a controlled DC link voltage.