Eia(Rs)485 Biasing Requirements; K-Bus; Figure 169: Rs485 Biasing Circuit - GE P4A Technical Manual

Micom p40 agile single br eaker multi-end current differential ied (non distance)
Table of Contents

Advertisement

Chapter 17 - Communications
3.2.1

EIA(RS)485 BIASING REQUIREMENTS

Biasing requires that the signal lines be weakly pulled to a defined voltage level of about 1 V. There should only be
one bias point on the bus, which is best situated at the master connection point. The DC source used for the bias
must be clean to prevent noise being injected.
Note:
Some devices may be able to provide the bus bias, in which case external components would not be required.
6 – 9 V DC
Master
V01000

Figure 169: RS485 biasing circuit

Warning:
It is extremely important that the 120 Ω termination resistors are fitted. Otherwise
the bias voltage may be excessive and may damage the devices connected to the
bus.
3.3

K-BUS

K-Bus is a robust signalling method based on RS485 voltage levels. K-Bus incorporates message framing, based on
a 64 kbps synchronous HDLC protocol with FM0 modulation to increase speed and security.
The rear interface is used to provide a permanent connection for K-Bus, which allows multi-drop connection.
A K-Bus spur consists of up to 32 IEDs connected together in a multi-drop arrangement using twisted pair wiring.
The K-Bus twisted pair connection is non-polarised.
It is not possible to use a standard EIA(RS)232 to EIA(RS)485 converter to convert IEC 60870-5 FT1.2 frames to K-
Bus. A protocol converter, namely the KITZ101, KITZ102 or KITZ201, must be used for this purpose. Please consult
General Electric for information regarding the specification and supply of KITZ devices. The following figure
demonstrates a typical K-Bus connection.
346
180 Ω bias
120 Ω
180 Ω bias
0 V
Slave
Slave
P54A/B/C/E
120 Ω
Slave
P54xMED-TM-EN-1

Advertisement

Table of Contents
loading

This manual is also suitable for:

P54bP54eP54c

Table of Contents