P54A/B/C/E
MENU TEXT
This cell is used to select the output relay contacts that will be tested when the 'Contact Test' cell is set to 'Apply Test'.
Test Pattern
This cell is used to select the output relay contacts that will be tested when the 'Contact Test' cell is set to 'Apply Test'.
Contact Test
When the 'Apply Test' command in this cell is issued the contacts set for operation (set to '1') in the 'Test Pattern' cell change state. After the
test has been applied the command text on the LCD will change to 'No Operation' and the contacts will remain in the Test State until reset
issuing the 'Remove Test' command. The command text on the LCD will again revert to 'No Operation' after the 'Remove Test' command has
P54xMED-TM-EN-1
COL
ROW
DEFAULT SETTING
0F
0E
0x0
0F
0F
No Operation
DESCRIPTION
Relay 13
Relay 14
Relay 15
Relay 16
Relay 17
Relay 18
Relay 19
Relay 20
Relay 21
Relay 22
Relay 23
Relay 24
Relay 25
Relay 26
Relay 27
Relay 28
Relay 29
Relay 30
Relay 31
Relay 32
[Binary Flag (32) Indexed String]
Relay 1
Relay 2
Relay 3
Relay 4
Relay 5
Relay 6
Relay 7
Relay 8
Relay 9
Relay 10
Relay 11
Relay 12
Relay 13
Relay 14
Relay 15
Relay 16
Relay 17
Relay 18
Relay 19
Relay 20
Relay 21
Relay 22
Relay 23
Relay 24
Relay 25
Relay 26
Relay 27
Relay 28
Relay 29
Relay 30
Relay 31
Relay 32
[Binary Flag (32) Indexed String]
No Operation
Apply Test
Remove Test
[Indexed String]
Appendix B - Settings and Signals
AVAILABLE OPTIONS
B129

Advertisement

Table of Contents
loading

This manual is also suitable for:

P54bP54eP54c

Table of Contents