Eia(Rs) 485 Connections; Output Relay Connections; Usb Connection; Case Dimensions - GE P50 Agile P253 Technical Manual

Motor protection relay
Table of Contents

Advertisement

10 Installation
2.3.3.6

EIA(RS) 485 Connections

For connecting the EIA (RS485), use 2-core screened cable with a maximum total length of 1000 m or
200 nF total cable capacitance.
A typical cable specification would be:
• Each core: 16/0.2 mm
• Nominal conductor area: 0.5 mm
• Screen: Overall braid, PVC sheathed
There is no electrical connection of the cable screen to the device. The link is provided purely to link
together the two cable screens.
2.3.3.7

Output Relay Connections

These should be wired with 1 mm PVC insulated multi-stranded copper wire terminated with M4 ring
terminals.
2.3.3.8

USB Connection

The IED has a type B USB socket on the front panel. A standard USB printer cable (type A one end,
type B the other end) can be used to connect a local PC to the IED. This cable is the same as that
used for connecting a printer to a PC.
2.4

Case Dimensions

Figure 9: Case dimensions
Note:
10-10
2
copper conductors, PVC insulated
All dimensions are in mm.
2
per core
P50 Agile P253
P253/EN M/C